Original Article |
2004, Vol.26, No.4, pp. 509-519
Thermal behavior of crimped spiral fin tube bank under dehumidifying process: A case study of inline arrangement
Atipoang Nuntaphan and Tanongkiat Kiatsiriroat
pp. 509 - 519
Abstract
Cross flow heat exchangers having crimped spiral fin and inline arrangement configurations under dehumidification are studied. The effect of tube diameter, fin spacing, fin height, transverse tube pitch are examined. From the experiment, it is found that the heat transfer and the frictional characteristics of the heat exchanger under dehumidification is close to that of the non-dehumidifying process. However, the air stream pressure drop and the heat transfer coefficient of the wet surface heat exchanger are higher and lower than those of the dry surface respectively. Moreover, equations are developed for predicting the f and the j factors of a tested heat exchanger. Results from the developed equations agree well with the experimental data.